198
to 0.
6.10 Group t, Auto-Tuning
t1 IM Motor Auto-Tuning
t1 parameters set the data for IM motor Auto-Tuning
Note: When running variable speed motors or vector motors, the voltage or frequency may be lower than
general-purpose motors. Therefore set the motor data according to the motor nameplate and perform
Auto-Tuning. After that, change the maximum output frequency in d1-02.
t1-01 Auto-Tuning Method Selection
Selects the method of Auto-Tuning..
No.
Name
Setting Range
Default
t1-01
Auto-Tuning Method Selection
0,1,2
0
0 : Rotational Auto-Tuning
1 : Stationary Auto-Tuning 1
2 : Stationary Auto-Tuning for Line-to-Line Resistance
t1-02 Motor Output Power
Sets the motor rated output power in kW units.
No.
Name
Setting Range
Default
t1-02
Motor Output Power
0.00 to 650.00 kW
Determined by o2-03, A1-06
Note:
1. The maximum motor rating the drive can run changes depending on the A1-06 (ND/HD Selection) setting.
2. 1HP (Horse Power) = 0.746kW
t1-03 Motor Rated Voltage
Sets the motor rated voltage according to the motor nameplate. If the motor is operating
above base speed, enter the voltage base speed here.
Variable speed motors and vector motors may have lower voltage or frequency than the
general-purpose ones. Therefore make sure the data entered matches the motor test report.
Enter the no-load voltage in this parameter for better control precision. If the motor test report