230
-10 30 40 50
P7-05
(Ambient Temperature
Setting: )
55
70
85
100
Drive rated current
(%)
P7-14=1 Side-by-side
mounting
P7-14=0 IP00
P7-14=2 NEMA 1
10.2 Altitude Derating
The most appropriate altitude to install the drive is below 1000m.
The drive rated voltage and the rated output current must be derated for 1% per 100 m
for drive installations from 1000 m to 3000 m altitude.