104
suppression current
value
(overcurrent) or oL1 (motor overload) and oL2
(drive overload) occur, reduce the n3-06 setting.
(The inverter rated current is 100%)
Group o, Keypad Function Settings
Frequency Command
Setting/Display Unit
0 : Use units of 0.01 Hz
1 : Use units of 0.01% (100% as maximum output
frequency)
2 : Use units of min-1 (automatically calculated by
maximum output frequency and number of motor
poles)
3 : Use user-defined units (defined by o1-02 and
o1-03)
Sets unit of
frequency-related
parameters of V/f
characteristics
0: in Hz
1: in min -1 (r/min)
User-Defined
Frequency Command
Setting/Display
Default: Determined by
o1-00
Min.: 1
Max.: 60000
Frequency
Command
Setting/Display
Decimal Places
Default: Determined by
o1-00
Min.: 0
Max.: 3
o2: Multi-Function Selection
LO/RE
(LOCAL/REMOTE)
Key Function
Selection
Enables or disables LO/RE key on the keypad.
0 ∶ Disabled
1 ∶ Enabled
Switches between Local and Remote Operation
STOP Key Function
Selection
Enables or disables the STOP key on the keypad
when the drive is controlled from a remote
source.
0 ∶ Disabled
1 ∶ Enabled
The STOP key always stops drive operation even
if the command source is not set to the keypad.