92
Parameter
Name
Description
Setting Range
action selection
and display ANL
2 : Speed to 0Hz and display ANL
3 : Stop immediately and show ACE
E3-11
Terminal A2 Input
Filter Time
Sets the terminal A2 primary delay filter time,
which can eliminate the interference.
Default: 0.05 s
Min.: 0.00 s
Max.: 2.00 s
E3-12
Analog Input
Terminal Enable/
Disable Selection
Enables the analog inputs when Multi-Function
Terminal Input E1-□□ = 41 (Multi-Function
Analog Input Selection).
0: Both Terminal A1 and A2 Disabled
1: Only Analog Input Terminal A1 Enabled
2: Only Analog Input Terminal A2 Enabled
3: Both Terminal A1 and A2 Enabled
Default: 3
Range: 0, 1, 2, 3
E3-13
A1 minimum input
A1 minimum input. When A1 original signal is less
than E3-13, it will be limited to E3-13.
Default: 0.0 V
Min.: 0.00 V
Max.: 9.9 V
E3-14
A2 minimum input
A2 minimum input. When the AI original signal is
less than E3-14, it will be limited to E3-14.
Default: 0.0 V
Min.: 0.0 V
Max.: 9.9 V
E4: Multi-Function Analog Output
E4-00
Terminal FM Signal
Level Selection
0 0 to 10 V
1 -10 to 10 V
Default: 0
Range: 0, 1
E4-01
Terminal FM
Monitor Selection
Selects the terminal FM monitor.
0 : Frequency Command
1 : Output Frequency
2 : Output Current
3 : Motor Speed
4 : Output Voltage
5 : DC Voltage
6 : Output Power
7 :Torque Command
8 : AI1 Input
9 : AI2 Input
10 : Soft Starter Output Frequency
11 :Pulse Train Input
12 : No function
Default: 1
Range: 0 to 12
E4-02
<4>
Terminal FM
Monitor Gain
Sets the terminal FM monitor gain.
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
E4-03
Terminal FM
Sets the terminal FM voltage bias.
Default: 0.0 %