93
Parameter
Name
Description
Setting Range
<4>
Monitor Voltage
Bias
Min.: -999.9 %
Max.: 999.9 %
E4-04
Terminal AM Signal
Level Selection
0: 0 to 10 V
1: 0 to 20 mA
2: 4 to 20 mA
Default: 0
Range: 0, 1, 2
E4-05
Terminal AM
Monitor Selection
Selects the terminal AM monitor.
0 : Frequency Command
1 : Output Frequency
2 : Output Current
3 : Motor Speed
4 : Output Voltage
5 : DC Voltage
6 : Output Power
7 : Torque Command
8 : AI1Input
9 : AI2Input
10: Soft Starter Output Frequency
11 :Pulse Train Input
12: No function
Default: 2
Range: 0 to 12
E4-06
<4>
Terminal AM
Monitor Gain
Sets the terminal AM gain.
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
E4-07
<4>
Terminal AM
Monitor Voltage
Bias
Sets the terminal AM voltage bias.
Default: 0.0 %
Min.: -999.9 %
Max.: 999.9 %
E5:Pulse Train Input/ Output
E5-00
Pulse Train Input
Function Selection
Selects the function for terminal RP.
0 Frequency Command
1 PID Feedback
2 PID Target
3 Speed Detection (Closed-Loop V/F Control)
(Only enabled when Motor 1 is selected in V/F
control method)
Default: 0
Range: 0, 1, 2, 3
E5-01
<4>
Pulse Train Input
Scaling
Sets the frequency equal to 100% frequency in Hz.
Default: 1440 Hz
Min.: 100 Hz
Max.: 32000 Hz
E5-02
<4>
Pulse Train Input
Gain
Sets the level of the input gain to terminal RP.
Default: 100.0%
Min.: 0.0 %
Max.: 1000.0 %
E5-03
Pulse Train Input
Sets the level of the input voltage bias when no
Default: 0.0%

Related product manuals