94
signal (0Hz) is input to terminal RP.
Pulse Train Input
Filter Time
Sets the pulse train input primary filter time in
seconds.
Default: 0.10 s
Min.: 0.00 s
Max.: 2.00 s
Pulse Train Input
Minimum
Frequency
Sets the minimum frequency detected by the
pulse train input. Enabled when E5-00 = 0, 1, 2.
Default: 0.5 Hz
Min.: 0.1 Hz
Max.: 1000.0 Hz
Pulse Train Monitor
Selection
Sets the function of pulse train output terminal
MP
0 : Frequency Command
1 : Output Frequency
2 : Soft Starter Output Frequency
3 : PID Feedback Value
4 : PID Target Value
Pulse Train Monitor
Scaling
Sets the pulse train output frequency when the
specified monitor item is at 100%.
Default: 1440 Hz
Min.: 100 Hz
Max.: 32000 Hz
Terminal RP
Function Selection
0:Pulse train input
1:PWM signal input
Default: 0
Min.: 0
Max.: 1
Default: 1
Min.: 1
Max.: 100
Default: 100 ms
Min.: 1 ms
Max.: 999 ms
E6: Optional Communication Card Settings
Torque command is
given by
communication
0 : Torque command is given by AI
1 : Torque command can be given by
communication
Sets the drive station address.
Default: 1
Range: 1 to 31
RS-485
Communication
Baud Rate Setting
Sets the baud rate for terminals SG(+) and SG(-) of
RS-485 communication.
0: 1200 bps (bit/sec)
1: 2400 bps
2: 4800 bps