95
Parameter
Name
Description
Setting Range
3: 9600 bps
4: 19200 bps
5: 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
E6-08
RS-485
Communication
Parity Selection
Selects the communication parity for terminals
SG(+) and SG(-) of RS-485 communication.
0: 8, N, 2 (Modbus RTU)
1: 8, N, 1 (Modbus RTU)
2: 8, E, 1 (Modbus RTU)
3: 8, O, 1 (Modbus RTU)
4: 8, N, 2 (Modbus ASCII)
5: 8, N, 1 (Modbus ASCII)
6: 8, E, 1 (Modbus ASCII)
7: 8, O, 1 (Modbus ASCII)
8: 7, N, 2 (Modbus ASCII)
9: 7, N, 1 (Modbus ASCII)
10: 7, E, 1 (Modbus ASCII)
11: 7, O, 1 (Modbus ASCII)
Default: 1
Range: 0 to 11
E6-09
Communication
Fault Detection
Enables or disables the communication fault
detection
0: Disabled
Default: 0.0
Range: 0.0~10.0s
E6-10
Transmit Wait Time
Sets the wait time between sending and receiving
data.
Default: 5ms
Range: 0 to 65 ms
E6-11
Drive Operation
During
Communication
Failure
0 : Display CE Alarm Only. Drive continues
operation.
1 : Display CE Fault. Drive coasts to stop.
Default:: 0
Range: 0 to 1
E6-12
Communication
frequency command
storage selection
0 : Do not store
1 : Storage
Default: 1
Range: 0 to 1
E6-13
Communication
frequency command
Sets communication frequency command
Default: 0.00 HZ
Range: 0.00 ~ 400.00
Hz
Group P, Protections
P1: Motor Protection Function
P1-00
Motor Protection
Function Selection
0 : Disabled
(Motor Overload Protection Disabled)
Default: 0
Range: 0 to 5