EasyManua.ls Logo

LiteOn EVO600043S1D5E20F - Page 60

LiteOn EVO600043S1D5E20F
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
Parameter
Name
Description
Setting Range
regulation (AVR)
1 : AVR is enabled
Range: 0, 1
Max.: 2
P3: Stall Prevention
P3-00
Stall Prevention
during
Acceleration
0 Disabled
1 Enabled the value set in P3-01.
Acceleration stops when the output current
exceeds the value set in P3-01. Acceleration
continues when the output current drops 15%
below the value set in P3-01.
Default: 1
Range: 0, 1
P3-01
Stall Prevention
Level during
Acceleration
Sets the output current level to activate the Stall
Prevention function during acceleration.
Default: 150%
Min.: 0%
Max.: 180
P3-02
Stall Prevention
Limit during
Acceleration
Sets the lower limit of Stall Prevention in the
constant power range as a percentage of the
drive rated output current.
Default: 50%
Min.: 0 %
Max.: 100 %
P3-03
Stall Prevention
during
Deceleration
0 : Disabled
The drive decelerates according to the set
deceleration time
1 : Enabled (Without Braking Resistor)
Default: 1
Range: 0, 1
P3-04
Stall Prevention
Level during
Deceleration
Sets the voltage level to activate the Stall
Prevention function during deceleration.
Default: 395V
Min.: 330V
Max.: 410V <3>
P3-05
Stall Prevention
during Run
0 : Disabled
1 : Enabled (Deceleration Time 1)
2 : Enabled (Deceleration Time 2)
Default: 1
Range: 0, 1, 2
P3-06
Stall Prevention
Level during Run
Sets the current level to activate the Stall
Prevention function during run.
Default: 150%
Min.: 30%
Max.: 180
P4: Frequency Detection
P4-00
Frequency
Detection Level
Sets the detection level and width for the multi-
function output terminal.
Default: 30.0 Hz
Min.: 0.0 Hz
Max.: <5>
P4-01
Frequency
Detection Width
Default: 2.0 Hz
Min.: 0.1 Hz
Max.: 25.5 Hz
P4-02
Frequency
Command Loss
Detection
Selection
Sets the drive operation when a frequency
command loss is detected.
0: Drive Stop
1: Continue operation according to the setting
Default: 0
Range: 0, 1

Other manuals for LiteOn EVO600043S1D5E20F