3 Troubleshooting (continued)
Service Manual
45
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Fan Speed Low 1
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The actual fan 1 RPM is 30% lower than
what is being called for.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting of the
Crest Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
Check the wiring connections at fan 1 and at the
main control board.
Replace the fan.
Blown fuse.
• Replace fuse F2 on the control board, see page 36
of this manual.
Fan Speed Low 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The actual fan 2 RPM is 30% lower than
what is being called for.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting of the
Crest Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
Check the wiring connections at fan 2 and at the
main control board.
Replace the fan.
Blown fuse.
• Replace fuse F2 on the control board, see page 36
of this manual.
Fan Speed High 1
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The actual fan 1 RPM is 30% higher than
what is being called for.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting of the
Crest Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Check the wiring connections at the fan and at the
main control board.
Replace the fan.
Fan Speed High 2
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART TOUCH
display
to reset.)
The actual fan 2 RPM is 30% higher than
what is being called for.
Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 2 - General Venting of the
Crest Installation and Operation Manual for
proper lengths.
Check for obstruction or blockage in the vent/air
intake pipes or at terminations.
• Check the wiring connections at the fan and at the
main control board.
Replace the fan.

Other manuals for Lochinvar Crest 1.5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lochinvar Crest 1.5 and is the answer not in the manual?

Lochinvar Crest 1.5 Specifications

General IconGeneral
BrandLochinvar
ModelCrest 1.5
CategoryBoiler
LanguageEnglish

Related product manuals