EasyManuals Logo

LS Industrial Systems iS7 User Manual

LS Industrial Systems iS7
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
iS7 Ethernet Option Manual
36
Attribute
ID
Access
Attribute
Name
Range
Definition
24000 frequency in [rpm] unit.
8 Get/Set
SpeedRef
0~
24000
Give reference on the
target frequency in [rpm]
unit. For this, the DRV-07
Freq Ref Src must have
been set up to FieldBus.
9 Get Actual Current
0~111.
0 A
Monitors present current
by 0.1 A unit basis.
29 Get
Ref.From
Network
0
The frequency reference
source is not the
DeviceNet
communication.
1
The frequency reference
source is the DeviceNet
communication.
100 Get Actual Hz
0~400.
00 Hz
Monitors present
operating frequency by Hz
unit.
101 Get/Set
Reference Hz
0~400.
00 Hz
When the DRV-07 Freq
Ref Src is set to
8.FieldBus, the reference
frequency can be set up
through communication.
102 Get/Set
Acceleration
Time
(Note2)
0~600
0.0 sec
Set-up/monitor Inverter
acceleration time.
103 Get/Set
Deceleration
Time
(Note3)
0~600
0.0 sec
Set-up/monitor Inverter
deceleration time.
(Note1) Related with the DRV-10 Torque Control and APP-01 App mode.
If the DRV-10 Torque Control is set to ‘Yes,’ the Drive Mode
becomes “Torque Control,” and if the APP-01 App mode is set to
Proc PID, MMC, the Drive Mode becomes “Process Control
(e.g.PI).”
(Note2) DRV-03 Acc Time value.
(Note3) DRV-04 Dec Time value.