iS7 Ethernet Option Manual
38
12. Lost Command
(1) Inverter Keypad Parameter
Code
Number
Set Value Description
PRT-12
"None"
"Free-Run"
"Dec"
"Hold Input"
"Hold Output"
"Lost Preset"
If a Lost Command
sets up the Inverter action.
(Note1)
PRT-13
Lost Cmd
Time
1.0 0.1~120.0 sec
0 0~600.00 Hz
Sets up speed of
Preset
(Note1) Lost Command Mode
Set Value Function
"None"
Maintains the previous status
occurs and Free Run stopped.
"Dec"
deceleration time.
"Hold Input"
previous operation reference.
"Hold Output"
previous operation speed.
"Lost Preset"
speed set up in the PRT-14.
(2) Modbus TCP Lost Command Status
If the Modbus TCP receives no data from Client for 100msec, the
Option becomes Lost Command status, and after the time set up in the
PRT-13, the Inverter operates according to the settings in the PRT-12.