GIPAM
GIPAMGIPAM
GIPAM-
--
- 115FI RELAY SETTING
115FI RELAY SETTING115FI RELAY SETTING
115FI RELAY SETTING
Protection relay
Protection relayProtection relay
Protection relay
Operation type
Operation typeOperation type
Operation type
Operating value setting / Increase & Decrease, Operating
Operating value setting / Increase & Decrease, Operating Operating value setting / Increase & Decrease, Operating
Operating value setting / Increase & Decrease, Operating
time
timetime
time
Remark
RemarkRemark
Remark
HIGH
Setting : Off, 2~24/1In (In = 5A)
Operating time : 0.04~60.0/0.01s
OCR(50/51)
LOW
Setting : Off, 0.2~10.0/0.1In
Operating time : 0.05~1.20/0.01
Definite time : D2,D4,D8
Inver time curve: SI, VI, EI, LI
OUT MODE : --, AL, TP
HIGH
Setting : Off, 0.5~8.0/0.5In
Operating time : 0.04~60.0/0.01s
LOW
Setting : Off, 0.1~0.5/0.02In
Operating time : 0.05~1.20/0.01
Definite time : D2,D4,D8
Inver time curve : SI, VI, EI, LI
OUT MODE : --, AL, TP
OCGR
(50/51N)
OCGR block Block Time : 0.1~60.0/0.1s
OCGR function is blocked
during the setting time when
starting motor (Applying over 2A
of phase current).
SGR
(67G)
-
Io setting : Off, 0.6~3.6/0.2Ion ( Ion=1.5mA )
Vo setting : 0.1~0.4/0.02Von ( Von=190V )
MTA: 45˚
Operating time : 0.1~60.00/0.01s
GR MODE : ON/OFF (Only lo operates under GR MODE)
Non-earth type
Definite time
OUT MODE : --, AL, TP
HIGH
Setting : OFF, 0.80~1.60Vn/0.02Vn (Vn = 100 or 110V)
Operating time : 0.1 ~ 60.0s / 0.01s
OVR
(59)
LOW
Setting : OFF, 0.80~1.60Vn/0.02Vn
Operating time : 0.1 ~ 60.0s / 0.01s
Definite time
OUT MODE : --, AL, TP
HIGH
Setting : OFF, 0.20~0.90Vn/0.02Vn
Operating time : 0.1 ~ 60.0s / 0.01s
LOW
Setting : OFF, 0.20~0.90Vn/0.02Vn
Operating time : 0.1 ~ 60.0s / 0.01s
Definite time
OUT MODE : --, AL, TP, TA
UVR
(27)
UVR LOCK Do not operate under 15V ( 3 phase voltage)
HIGH
Setting : OFF, 0.10~0.40Von/0.02Von (Von=190V)
Operating time : 0.1 ~ 60.0s / 0.01s
OVGR
(64)
LOW
Setting : OFF, 0.10~0.40Von/0.02Von (Von=190V)
Operating time : 0.1 ~ 60.0s / 0.01s
Definite time
OUT MODE : --, AL, TP
3.
3. 3.
3. Protecti
ProtectiProtecti
Protection
onon
on Relay
Relay Relay
Relay