5. PT / CT SETTING
5 . P T / C T S E T T I N G
6 . T I M E
The following subordinate menus are available from 5. PT/CT SETTING.
1 . W I R I N G
2 . C T S E T
3 . P T S E T
4 . S e c o n d P T V o l
5-1) WIRING: The value can be changeable by pressing DEC/INC key (1P2W, 1P3W, 3P3W, 3P4W)
5-2) CT Set: The value can be changeable by pressing DEC/INC key (5~6000/1UNIT)
5-3) PT Set: The value can be changeable by pressing DEC/INC key (110~345000/1UNIT)
5-4) SECOND PT VOL: The value can be changeable by pressing DEC/INC key (100, 110)
* Caution: If changing the setting value of primary /secondary CT and PT, the values of WH and VARH are reset.