Chapter 8 Power Module
8-3
8.2 Specifications
Items XGP-ACF1 XGP-ACF2 XGP-AC23 XGP-DC42
Rated input voltage AC100V - AC240V AC200V - AC240V DC24V
Input voltage range AC85V ~ AC264V AC170V ~ AC264V -
Input frequency 50 / 60 Hz (47 ~ 63 Hz) -
Inrush current 20APeak or less 80APeak or less
Efficiency 65% or more 60% or more
Input fuse Built-in (user no change), UL standard (Slow Blow Type)
Input
Allowable moment
shutdown
within 10 ms
Output voltage DC5V (±2%) DC5V (±2%)
Output current 3 A 6 A 8.5 A 6A
Overcurrent protect 3.2A or more 6.6 A or more 9A or more 6.6 A or more
Output
1
Overvoltage protect 5.5V ~ 6.5V
Output voltage DC24V (±10%)
Output current 0.6 A
Overcurrent protect 0.7 A or more
Output
2
Overvoltage protect None
- -
Application RUN contact (Refer to the section 8.3)
Rated switching
voltage/current
DC24V, 0.5A
Minimum switching
load
DC5V,1
Response time
OffOn/ OnOff: 10 or less/12 or less
Relay
Output
Life
Mechanical: More than 20,000,000 times
Electrical: More than 100,000 times at rated switching voltage/current
RUN signal output Relay output, Rating: DC24V, 0.5A
Voltage indicator Output voltage normal, LED On
Cable specification 0.75 ~ 2 mm
2
Compressed terminal RAV1.25-3.5,RAV2-3.5
Weight 0.4 kg 0.6 kg 0.5 kg
Notes
1) Allowable Momentary Power Failure Time
The time that input voltage keeps normal output voltage (normal operation) in the state that AC110/220V
voltage is below rated value (AC85 / 170V).
2) Over current protection
(1) If the current over the standard flows in DC5V, DC24V circuit, the over current protection device
shutdowns the circuit to stop the system.
(2)
In case of over current, remove the causes such as lack of current capacity or short circuits etc. and
then restart the system.
3) Over voltage protection
If the voltage over the standard is applied in DC5V circuit, the over voltage protection device shutdowns
the circuit to stop the system.