EasyManua.ls Logo

LSIS XGK-CPUU - Data Latch Area Settings

LSIS XGK-CPUU
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 5 Program Configuration and Operation Method
5 - 24
5.5.5 Data Latch Area Setting
When PLC stops and restarts the data required for operation or the data occurred during operation, if you
want to keep and use those data, data latch can be used and it is available to use a certain area of some
data device as latch area by parameter setting.
The below shows the features for latch device.
Device 1
st
latch 2
nd
latch Features
P X X Image area to save the state of I/O device
M O O Internal device area
K X X Device keeping the device state during power shutdown
F X X System flag area
T O O Timer related area (Bit/words both)
C O O Counter related area (Bit/words both)
S O O Relay for step control
D O O General words data save area
U X X Analog Data Register (latch disabled )
L X X
High speed link/P2P Service state device of communication
module (latch enabled)
N X X
P2P Service address area of communication module (latch
enabled)
Z X X Index dedicated Register (latch disabled)
R X X Flash memory dedicated area (latch enabled)
Notes
1) K, L, N, R devices are basically latched.
2) K, L, R devices operate like the 1
st
Latch that clears data by using Overall Reset or the CPU
module D.CLR switch.
3) For more information, refer to the Online section of the XG 5000 user’s manual.

Table of Contents