7.2.3 16 point DC24V Input Module (Source Type)
DC input module
Model
Specification
XGI-D22B
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
Input Derating None
On Voltage/Current DC19V or higher / 3 mA or higher
Off Voltage/Current DC11V or lower / 1.7 mA or lower
Input resistance
About 5.6 kΩ
Off On
1ms/3ms/5ms/10ms/20ms/70ms/100ms (set by CPU parameter)
Default:3ms
Response
time
On Off
1ms/3ms/5ms/10ms/20ms/70ms/100ms (set by CPU parameter)
Default:3ms
Insulation pressure AC560V rms/3 Cycle (altitude 2000m)
Insulation resistance 10 or more by megger
Common Method 16 point / COM
Proper cable size Twisted pair 0.3~0.75 (external diameter 2.8mm or less)
Proper compressed terminal R1.25-3 (not allowed to use a sleeve attached compressed terminal.)
Current consumption () 30mA
Operation indicator Input On, LED On
External connection method 18 point terminal block connector (M3 X 6screw)
Weight 0.12 kg
Circuit configuration
Terminal
block
Contact
TB1
P0
TB2 P1
TB3 P2
TB4 P3
TB5 P4
TB6 P5
TB7 P6
TB8 P7
TB9 P8
TB10 P9
TB11 PA
TB12 PB
TB13 PC
TB14 PD
TB15 PE
TB16 PF
TB17 COM
TB18 NC
DC24V
Internal
circuit
R
1
F
0
TB1
COM
Photocoupler
Terminal block no.
TB16
TB17
R
00
06
0D
COM
0
1
02
03
04
05
0A
0
B
0C
0F
0E
08
07
09

Table of Contents