Chapter 7 I/O Module
7-13
7.3.2 16 point Relay Output Module
Relay Output Module
Model
Specification
XGQ-RY2A
Output point 16 point
Insulation method Relay insulation
Rated load voltage/current
DC24V 2A(resistive load) / AC220V 2A(COSΨ = 1)
Min. load voltage/current DC5V / 1mA
Max. load voltage/current AC250V, DC125V
Off leakage current 0.1mA (AC220V, 60Hz)
Max. on/off frequency 3,600times/hr
Surge absorber None
Mechanical 20 million times or more
Rated load voltage/current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 times or more
Service life
Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 times or more
Off → On
10 ms or less
Response
time
On → Off
12 ms or less
Common method 16 point / 1COM
Current consumption 500mA (when all points On)
Operation indicator Output On, LED On
External connection method 18 point terminal block connector (M3 X 6screw)
Weight 0.17kg