Chapter 3. Standard Specification
3-1
Chapter 3. Standard Specification
3.1 General Standards
XGT Panel’s general standard is as follows.
No. Category Standard Related standard
1
Ambient
operating
temperature
0
℃∼
+50
℃
-
2
Storage
temperature
-20
℃∼
+60
℃
-
3
Operating
humidity
10
∼
85%RH, non-condensing. -
4
Storage
humidity
10
∼
85%RH, non-condensing.
-
5
Vibration
resistance
Occasional vibration count -
Frequency Acceleration Amplitude
10 times for each
IEC 61131-2
5 ≤ f < 9
㎐
- 3.5 mm
9 ≤ f ≤ 150
㎐
9.8
㎨
-
Continuous vibration
Frequency Acceleration Amplitude
5 ≤ f < 9
㎐
- 1.75 mm
9 ≤ f ≤ 150
㎐
4.9
㎨
-
6
Shock
endurance
* Maximum shock acceleration: 147
㎨
(15G)
* Duration time: 11
㎳
* Pulse wave: half sine pulse (3 shocks per axis, on X, Y, Z axis)
IEC 61131-2
7
Noise
Immunity
Square wave
Impulse noise
AC: ±1,500V
DC: ±1,000V
LSIS
Standard
Electrostatic
discharge Immunity
±
6 kV (Discharge by contact)
IEC 61131-2
IEC 61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1000 MHz, 10 V/m
IEC 61131-2
IEC 61000-4-3
Fast transient &
Burst noise
Category Power module
Communication
interface
IEC 61131-2
IEC 61000-4-4
Voltage 2 kV 1 kV
8 Environment
Free from corrosive gases and excessive dust -
9
Operating
height
Up to 2,000m (6,562 ft) -
10
Pollution degree
Less than 2
-
11
Cooling method