Chapter 3. Standard Specification
3-2
Remark
(1) IEC(International Electro technical Commission)
: International private group facilitating international cooperation of electric/electronic standardization, issuing international
standards and operating the compliance evaluation systems.
(2) Pollution degree
: As an index representing the pollution degree of an environment to determine the insulation of a device, pollution degree 2
generally means the status generating non-conductive contamination. However, it also contains the status generating
temporarily conduction due to condensation.
(3) Radiated electromagnetic field noise for XP30-BTE(TTE) is 80 ~ 1000MHz, 10 V/m
(All others are same as shown on the table)
(1) General Specification for XP40-TTA(TTE)
No.
Standard Related standard
1
Operating
Temperature
0
℃∼
+50
℃
-
2
Storage
Temperature
-20
℃∼
+60
℃
-
3
Operating
Humidity
10
∼
85%RH, non-condensing.
-
4
Storage
Humidity
10
∼
85%RH, non-condensing.
-
5
Vibration
Resistance
Occasional vibration count -
Frequency Acceleration Frequency
10 times for each
X, Y, Z axis
IEC 61131-2
5 ≤ f < 9
㎐
-
5 ≤ f < 9
㎐
9 ≤ f ≤ 150
㎐
9.8
㎨
(1G) 9 ≤ f ≤ 150
㎐
Continuous vibration
Frequency Acceleration Frequency
5 ≤ f < 9
㎐
-
5 ≤ f < 9
㎐
9 ≤ f ≤ 150
㎐
4.9
㎨
(0.5G) 9 ≤ f ≤ 150
㎐
6
Shock
Endurance
* Maximum shock acceleration: 147
㎨
(15G)
* Duration time: 11
㎳
* Pulse wave: half sine pulse (3 shocks per axis, on X, Y, Z axis)
IEC 61131-2
7
Noise
Immunity
Square wave
Impulse noise
DC: ±800V
-
Electrostatic discharge
Immunity
±
4kV (Contact discharge)
IEC61000-4-2
Radiated
electromagnetic field
noise
80 ~ 1,000 MHz, 10 V/m
IEC61131-2
IEC61000-4-3
Fast transient &
Burst noise
Category
Communication
interface
IEC61131-2
IEC61000-4-4
Voltage
Free from corrosive gases and excessive dust -
9
Operating
height
Up to 2,000m (6,562 ft) -
10
Pollution
degree
2 or less
-