Chapter 9. File Backup through External Storage Equipment
9-5
In case USB storage equipment (or CF storage equipment) is removed during operation after setting the path for saving Logging
backup file as USB storage equipment (or CF storage equipment) and downloading the project into device, the designated system
alarm (HS951.0) is set. In case storage equipment is equipped again, alarm is reset.
In case USB storage equipment (or CF storage equipment) is removed during operation after setting the path for saving Recipe
backup file as USB storage equipment (or CF storage equipment) and downloading the project into device, the designated system
alarm (HS951.1) is set. In case storage equipment is equipped again, alarm is reset.
In case USB storage equipment (or CF storage equipment) is removed during operation after setting the path for saving Screen
Image backup file as USB storage equipment (or CF storage equipment) and downloading the project into device, the designated
system alarm (HS951.2) is set. In case storage equipment is equipped again, alarm is reset.
Internal address of the designated system alarm can be checked in XP-Builder as follows.