EasyManua.ls Logo

Lucent DDM-2000 OC-3 - Page 688

Lucent DDM-2000 OC-3
1224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
363-206-285 Trouble Clearing: TAP-112
Issue 2, February 2000 Page 2 of 16
DDM-2000 OC-3 MULTIPLEXER
3.
NOTE:
Local alarm or status conditions have a Source Address of the local
slot, line, port, channel, path, cross-connection, or operations interface
(DCC, X.25, etc.) where the event occurred. (See
Addresses
in the
Commands and Reports section of this manual.) Use the rtrv-alm:
command to get another report, if necessary.
Note the trouble indication in the Description column of the Active
Alarm and Status Report, starting with the highest alarm level (Minor)
listed in the Alarm Level column.
4. Use opr-aco; command to silence active audible office alarms, if required.
5. Find the trouble description in Table A for the highest alarm level and go to the
indicated step or procedure.