EasyManua.ls Logo

Mandik FDMB Series - Square Dampers in Gypsum Wall

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
60
120
400
variable **
100
400
variable **
60
120
400
variable **
100
**** Detail mounting and placementVRM-III page 12
* min. 110 - Concrete/ min. 125 - Aerated Concrete
100
100
150*
50***
60
120
*** Around the perimeter
Installation opening perimeter has to be
reinforced by standard drywall profiles.
100
50***
50***
50***
50***
Fire damper FDMB
Solid ceiling construction
Mortar or gypsum
Gypsum wall construction
Solid wall construction
Duct
Fire protection plate
of mineral wool
Mineral stone wool
Fire protection mastic
min. thickness 1 mm
Cement lime plate
min. thickness 15 mm
Stone wool resin bonded con-
taining toxic rubble as refriger-
ants, fire resistance EIS 90 min.
density 300 kg/m
th. 60 mm and 120 mm
Sheet metal a stiffener
U25x40x25
VRM-III****
** Dependent on the distance between
damper and fire separating

Related product manuals