EasyManuals Logo
Home>Manitowoc>Ice Maker>Indigo ID0322A

Manitowoc Indigo ID0322A User Manual

Manitowoc Indigo ID0322A
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
154 Part Number STH025 11/16
COLUMN 3  TXV FLOODING OR REFRIGERANT
OVERCHARGE
A loose or improperly mounted expansion valve
bulb causes the expansion valve to flood. Check bulb
mounting, insulation, etc., before changing the valve.
Verify refrigerant amount is correct by weighing
recovered refrigerant before replacing a TXV.
COLUMN 4  COMPRESSOR
Replace the compressor. To receive warranty credit, the
compressor ports must be properly sealed by crimping
and soldering them closed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc Indigo ID0322A and is the answer not in the manual?

Manitowoc Indigo ID0322A Specifications

General IconGeneral
BrandManitowoc
ModelIndigo ID0322A
CategoryIce Maker
LanguageEnglish

Related product manuals