EasyManua.ls Logo

MasterCool 53010

Default Icon
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3www.mastercool.com
Testing Range of Systems
R134a 260 - 320 psi 18 - 22 bar
R404A 405 - 465 psi 28 - 32 bar
R404C 405 - 465 psi 28 - 32 bar
R507 405 - 465 psi 28 - 32 bar
R22 405 - 465 psi 28 - 32 bar
R410A 550 - 610 psi 38 - 42 bar
• Open the output control valve (4) and open the ball valve (9) on the
leak testing gauge assembly for the nitrogen to flow into the system.
(If using a manifold, open the output control valve (4) and the low side
valve (13) on the manifold.)
• Make sure the required pressure is available on both gauges. (You may
need to turn the T handle (6) on the regulator to adjust to the required
pressure.)
• Once the pressure is equalized (make sure the black needle is aligned
with the red marker on the leak testing gauge assembly) close the ball
valve connection (9).
(If using a manifold, close the low side valve (13) on the manifold
making note of the pressure when the valve is closed.)
• Close the output control valve (4) on the regulator
• Disassemble the yelllow charging hose (11) from the regulator and
leave the system for a period of time (time is based on the size of the
system.)
After some time, look at the gauge, if there is a leak in the system the
pressure will have dropped from the original settting.
REGULATOR REMOVAL
Turn the cylinder valve off.
• Relieve the pressure on the regulator by opening the output control
valve (4). Both gauges should read zero.
• Slowly loosen the cylinder connection. There may still be some
pressure between the regulator and cylinder.
• Completely remove the regulator.
• Clean and store the regulator in its box to prevent damage.