Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.
19. Check out overall system operation by cycling
through light-off at minimum, interrupting pilot,
and allowing temperature control system to cycle
burner from minimum to maximum and return.
Recheck all safety system interlocks for proper
setting and operation.
NOTE: Typical gas firing control sequence for Maxon
burner is provided
only as a guide. Instructions
provided by complete system manufacturer incorpo-
rating Maxon burners take precedence.
For gas firing Model “400” OVENPAK
®
Burner
Light-off: Shut-down:
1. Close cocks, shut-off valve(s) 1. Close main &
2. Verify burner at low fire pilot gas cocks
3. Start recirculating/exhaust fans 2. Keep combustion
4. Start burner blower air blower running
5. Purge at least 4 air changes after shut-down long
6. Open pilot & main gas cocks enough to allow
burner to cool
WARNING: Test every UV installation for
dangerous spark excitation from ignitors and
other possible sources of direct or reflected UV
radiation. Use only gas-tight scanner
connections.
20. Before system is placed into full service,
instruct operator personnel on proper start-up
operation with shut-down of system, establishing
written instructions for their future reference.
Page 2100-S-7“400”, “200” OVENPAK
®
Burners
Start-Up Instructions
4/98