OM AGSB-5 11
Table 4, Digital Outputs
# Description Load Output OFF Output ON Voltage
1 Compressor Starter Contact Relay Compressor off Compressor on 120
2 M1 Contactor (fan 1) Contactor Coil Fans off Fans on 120
3 M2 Contactor (fan 2) Contactor Coil Fans off Fans on 120
4 M3 Contactor (fan 3) Contactor Coil Fans off Fans on 120
5 M4 Contactor (fan 4) Contactor Coil Fans off Fans on 120
6 M5 Contactor (fan 5 & 6) Contactor Coil Fans off Fans on 120
7 Load/Unload Pulse Solenoid Hold load slide Move load slide 24
8 Load/Unload Select Relay Unload Load 24
9 M7 Contactor (fan 7 & 8) Contactor Coil Fans off Fans on 120
10 Oil Return Line Solenoid Closed Open
11 Open
12 Open
13 EXV Close Signal Contact
EXV Follows
0 – 10 VDC
EXV Closed,
Ignores 0 – 10
VDC
10
These parameters are digital outputs from this controller. Their values are sent to the correct
pLAN addresses for use by other controllers or displays.
Setpoints
The following parameters are remembered during power off, are factory set to the
Default value, and can be adjusted to any value in the Range column.
The PW (password) column indicates the password that must be active in order to
change the setpoint. Codes are as follows:
O = Operator, password is 100
M = Manager
Entering a Password
The password is located in the unit controller only and can be found at SET, UNIT SPS on
the last menu conveniently located so that you can scroll up one menu to access the
Password Enter Screen.