25
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
A place protected from direct sunlight. Otherwise use an awning for protection, if necessary.
The location must not be susceptible to dust or oil mist.
2. INSTALLATION CLEARANCES
Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction
to smooth air flow. Select the coolest possible place where intake air should not be hotter than the
outside temperature.
Dimension A B C D
Minimum distance, mm/in
300/11.8 1000/39.4 300/11.8 500/19.7