OMM 1008-1 73
SET SETPOINTS
SET COMP#1 SPs (1)
Demand Limit=OFF
Minimum Amps=040%
Maximum Amps=100%
SET ALARM LMTs (1)
LowEvPrHold=33psi
LowEvPrUnld=31psi
LowEvPrStop=29psi
SET PASSWORD
Enter
Password:00000
No Access Given
SET COMP SPs (2)
StageMode =Normal
StageSequence# = 01
Max Compr ON = 01
SET ALARM LMTs (2)
HighCondPr =140psi
HiDschT-Load=170
o
F
HiDschT-Stop=190
o
F
SET PASSWORD (2)
Tech Password
00000 00000
No Access Given
SET COMP SPs (3)
StageDeltaT = 1.0
o
F
Stop-Start = 03 min
Start-Start = 40 min
SET ALARM LMTs (3)
WMC Compressor
Oilless Design
(blank mask page)
SET COMP SPs (4)
Full Load = 300 sec Name
Plate RLA 085
SET ALARM LMTs (4)
Surge Slp Str=20
o
F
Surge Tmp Run=06
o
F
MtrCurThrshld=10%
SET COMP SPs (5)
Nom Capacity = 0100T
HotGasBypass = 30%
SET ALARM LMTs (5)
Evap Freeze= 34.0°F
Cond Freeze= 34.0°F
SET COMP SPs (6)
InterLokTmr= 010sec
UnloadTimer = 030 sec
SET COMP SPs (7)
WMC Automatic
Vane Control
(blank mask page)
SET COMP SPs (8)
MAX KW = 76.0
Lag Start = 000Sec
Step Down = 060Sec
SET COMP SPs (9)
Protocol =M-BUS MSTR
Ident Number= 001
Baud Rate = 19200
SET COMP SPs (10)
Refrg Sat Pressure
Evp Offset =+00.0 psi
Cnd Offset = +00.0psi
SET COMP SPs (11)
ELWT Offset = +0.0
o
F