96
HEATPUMP
Indoor Outdoor Liquid Pipe Gas Pipe CFM
Refrigerant Charge
(kg/7.5m pipe length)
MDB075BR MMC075CR 1/2" 1" 2500 4.6
MDB100BR MMC100BR 5/8" 1-1/8" 3200 5.6
MDB125CR MMC125BR 5/8" 1-1/4" 4200 6.5
MDB150BR2 MMC075CR x 2 1/2" 1" 4600 4.6 x 2
MDB200BR2 MMC100BR x 2 5/8" 1-1/8" 6400 5.6 x 2
MDB250BR2 MMC125BR x 2 5/8" 1-1/4" 8000 6.5 x 2
MDB300BR3 MMC100BR x 3 5/8" 1-1/8" 9000 5.6 x 3
MDB350BR3 MMC100BR + MMC125BR x 2 5/8" 1-1/8" & 1-1/4" 10500 5.6 + 6.5 x 2
MDB400BR4 MMC100BR x 4 5/8" 1-1/8" 12000 5.6 x 4
MDB500BR4 MMC125BR x 4 5/8" 1-1/4" 15000 6.5 x 4
Remark:
With Scroll compressor and bi-flow TXV at the outdoor unit specification.
ADDITIONAL CHARGE
Based on liquid pipe size per meter length:
Liquid Pipe Size, inch Additional Charge, kg/meter
1/4” 0.02
5/16” 0.04
3/8” 0.05
1/2” 0.10
5/8” 0.17
3/4” 0.26
7/8” 0.37
Note: Refer to the table of the Recommended Maximum Pipe Length.