OM WGS-5 WGS 130A to 190A 91
Clear Cycle Tmr= no
Comp Size= XXX
Max Slide= XXX.X %
SET COMP SPs (2)
Circuit Mode=Enable
Slide Target= XXX.X%
Slide Control=auto
SET STARTER SPs (3)
Motor FLA= XXX amps
Motor RLA= XXX amps
The starter set points are stored in permanent memory on the starter and the Circuit control set
points will be reset to the values stored on starter when the Circuit control is powered up.
When the Circuit control is powered up the starter set points MUST be adjusted from the
Circuit control.
Ground Fault Enable, Ground Fault Trip Level, Rated RMS Voltage and CT Ratio set points
are NOT adjustable while the compressor is running.
SET STARTER SPs (4)
Ground Fault=No
GF Trip Level= XXX%
EXV Set Points
SET EXV SPs (1)
Manual EXV Pos= XXXX
EXV Control=auto
Service Pumpdown=No
SET EXV SPs (2)
Preopen Timer=XXXsec
Sensor Offsets
SET SENSOR OFFSET(1)
Evap Press= XX.X psi
Cond Press= XX.X psi
SET SENSOR OFFSET(2)
Suct Temp= X.X F
Disch Temp= X.X F
SET SENSOR OFFSET(3)
Slide min pos= XX%
Slide max pos= XX%