EasyManuals Logo

Megmeet MTC-08-NT User Manual

Default Icon
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
27
buffer for MTC#3
buffer for MTC#7
3.2.5 Programming
This section through the "man-machine interface +PLC+MTC" this application system to explain the
general use of MTC thermostat. Taking MEGMEET series PLC as an example, ModBus is used for
communication between man-machine interface and PLC, and McBus is used for communication
between PLC and MTC. PLC station number is 0 and MTC station number is 1. 1. Set the parameters of
MTC. See chapter 4 for the MTC wizard Settings.
2. With the D and M components open to the user, PLC and man-machine interface can be used to
monitor and measure MTC. Let's expand on that.
Note: the D elements listed in table 3-2 and the dedicated M elements in the attachment are the
dedicated soft elements of the thermostat. Users are not allowed to use them for other purposes.
MTC provide some dedicated D and M components. For dedicated M components, users can operate
directly (see appendix I list of MCbus dedicated M components). For the D element, the user can operate
through the five command words described above.
Read command 4
1. The main module defines the frame with the MCbus communication buffer. D component definitions
are shown in the following table
Table 3-3 Settings represent communication special meaning D element
2. MTC thermostat return the frame with the MCbus communication buffer. Take MTC#1 region as an
example: when D7532 and D7563 become 4, data can be read from MTC, up to 30 D elements can be
read at a time, as shown in the following table.
Table 3-4 D component definitions 1
D elements
Explanation
D elements
Explanation
D7532
4
D7548
0
D7533
CH1 measured value (PV)
D7549
CH1 multi-step current
execution segment
D7534
CH2 measured value (PV)
D7550
CH2 multi-step current
execution segment
D7535
CH3 measured value (PV)
D7551
CH3 multi-step current
execution segment
D7536
CH4 measured value (PV)
D7552
CH4 multi-step current
execution segment
D7537
0
D7553
0
D7538
0
D7554
0
D7539
0
D7555
0
D7540
0
D7556
0
D7541
CH1 heat control output value
D7557
Cool control output status
D7542
CH2 heat control output value
D7558
0
D7500
D7501
D7502~7530
D7531
MTC module station
number to be read
4
Meaningless
Meaningless

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Megmeet MTC-08-NT and is the answer not in the manual?

Megmeet MTC-08-NT Specifications

General IconGeneral
BrandMegmeet
ModelMTC-08-NT
CategoryThermostat
LanguageEnglish