42
value-set value) is smaller than the alarm
setting
5
Deviation
high/low
Alarm when the absolute value of
deviation (| measured value - setting
value |) is larger than the alarm setting
value
± input width
6
Band
Alarm when the absolute value of
deviation (| measured value - setting
value |) is smaller than the alarm setting
value
± input width
Waiting
for
alarm
7
Wait with the
high limit alarm
If the measured value is larger than the
alarm setting value, the measured value
will be ignored when the power is turn on
Input scope
8
Wait with the low
limit alarm
If the measured value is smaller than the
alarm setting value, the measured value
will be ignored when the power is turn on
Input scope
9
Wait with the
deviation high
alarm
If the deviation value (measured value -
set value) is larger than the alarm setting
value, the measured value will be ignored
when the power is turn on
± input width
10
Wait with the
deviation low
alarm
If the deviation value (measured value -
set value) is smaller than the alarm
setting value, the measured value will be
ignored when the power is switched on
± input width
11
Wait with the
deviation high
/low alarm
Alarm when the absolute value of
deviation (| measured value - setting
value |) is larger than the alarm setting
value, but the measured value will be
ignored when the power is switched on
± input width
Wait for
the
second
alarm
12
Wait again with
the deviation
high limit alarm
Alarm when the deviation (measured
value-set value) is greater than the alarm
set value, but the measured value will be
ignored when the power is turned on and
the set value changes
± input width
13
Wait again with
the deviation low
limit alarm
Alarm when the deviation (measured
value-set value) is greater than the alarm
set value, but the measured value will be
ignored when the power is turned on and
the set value changes
± input width
14
Wait again with
the deviation
high/low limit
alarm
When the absolute value of deviation (|
measured value - set value |) is larger
than the alarm setting value, the
measured value will be ignored when the
power is switched on and the set value
± input width