EasyManua.ls Logo

Megmeet MTC-08-NT - Page 46

Default Icon
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
alarm triggered by the measured value when the set value is changed (waiting), until the measured
value next triggers the alarm, as shown in figure 5-16.
Figure 5-16 Schematic diagram of the wait again the alarm
5.3.2 Alarm dead zone
In order to avoid repeated occurrence of the alarm state and non-alarm state when the
measured value fluctuates around the alarm setting value, the alarm dead zone (BFM # 604) can
be set. The alarm dead zone applies to all alarm types and all channels. See Figure5-17 ~ Figure
5-19.
Figure 5-17 Schematic diagram of high limit and deviation high
Figure 5-18 Schematic diagram of low limit and deviation low