ng running g running 1: Enabled
P12.02
Carrier wav
e frequency
Carrier wave
frequency
0.7~15.0KHz (minimum vector:
2k)
0.1 8.0
P12.03
PWM mode
optimization
PWM mode
optimization
Unit place: Enable the over
modulation
0: Disabled
1: Enabled
Tens place: Automatic adjustment
selection for carrier wave
frequency
0: No automatic adjustment
1: Automatic adjustment
Hundreds place: modulation
mode
0: Two-phase/ three-phase
switching
1: Three-phase modulation
Thousands place: Low frequency
carrier limit
0: Disable
1: Enable
1 1001 × ×
P12.04
Current loop
gain
selection
Current loop
gain
selection
0: Manual selection
1: Calculate automatically (after
tuning)
1 0 × ×
P12.05
Current loop
proportional
gain ACR-P
Current loop
proportional
gain
1~5000 1 1000 ×
P12.06
Current loop
integral time
ACR-I
Current loop
integral time
0.5~100.0ms 0.1 8.0 ×
P12.07
Anti-trip
function
enabling
Anti-trip
function
enabling
0: Disable
1: Enable
1 0 × ×
P12.08
Frequency
reduction
rate upon
voltage
compensati
on
Frequency
reduction
rate
0.00~99.99Hz/s 0.01 10.00 ×
P12.09
Pre-magneti
zing time
Pre-magnetiz
ing time
0.0~10.0s 0.1 0.0 × ×
P12.10
Minimum
flux
reference
value
Minimum flux
reference
value
10~150% 1 10
×
P12.11
Flux-weake
ning
adjustment
Flux-weakeni
ng
adjustment
0~10000 1 1000 ×