91
(P09.12)/2. It is positive when the
frequency is less than the central
point frequency
2: With central point, it is
(P09.12)/2. It is positive when the
frequency is larger than the
central point frequency
P09.14
Pulse input
filtering time
Pulse input
filtering time
0.00~10.00s 0.01s 0.05 ×
P09.15
Input
terminal
enabled
status
setting
Input
terminal
enabled
status
Binary setting:
0: Normal logical, enabled upon
connection
1: Inverted logical, enabled upon
disconnection
Unit place of LED:
BIT0~BIT3: X1~X4
Tens place of LED:
BIT0~BIT3: X5~X8
1 00 ×
P09.16
Virtual input
terminal
setting
Virtual input
terminal
setting
Binary setting:
0: Disabled
1: Enabled
Unit place of LED:
BIT0~BIT3: X1~X4
Tens place of LED:
BIT0~BIT3: X5~X8
1 00 ×
P09.17
Output
selection of
Multi-functio
nal output
terminal Y1
Output
selection of
Multi-function
al output
terminal Y1
0: Open collector output terminal
Y1
1: DO terminal output
1 0
×
P09.18
Open
collector
output
terminal Y1
Y1 function
selection
0: Drive in running state signal
(RUN)
1: Frequency arrival signal (FAR)
2: Speed non-zero detection
signal
3: Frequency level detection
signal (FDT1)
4: Frequency level detection
signal (FDT2)
5: Overload detection signal (OL)
6: Lockout for under-voltage (LU)
7: External fault stop (EXT)
8: Frequency upper limit (FHL)
9: Frequency lower limit (FLL)
10: Drive running at zero-speed
1 0 ×
P09.19
Open
collector
output
terminal Y2
Y2 function
selection
1 1 ×
P09.20
Relay RO1
output
function
selection
RO1 function
selection
1 15 ×
P09.21
Relay RO2
output
function
RO2 function
selection
1 16 ×