MI 3102(H) BT EurotestXE Technical specifications
96
10.8 Resistance to earth
10.8.1 Standard earthing resistance measurement – 3-wire
measurement
Measuring range according to EN61557-5 is 2.00 1999 .
(5% of reading + 5 digits)
Max. auxiliary earth electrode resistance R
C
...........100R
E
or 50 k (whichever is lower)
Max. probe resistance R
P
.......................................100R
E
or 50 k (whichever is lower)
Additional probe resistance error at R
Cmax
or R
Pmax.
.(10 % of reading + 10 digits)
Additional error at 3 V voltage noise (50 Hz) ...........(5 % of reading + 10 digits)
Open circuit voltage ................................................<30 VAC
Short circuit current ................................................< 30 mA
Test voltage frequency ...........................................125 Hz
Test voltage shape .................................................sine wave
Noise voltage indication threshold ..........................1 V (< 50 , worst case)
Automatic measurement of auxiliary electrode resistance and probe resistance.
Automatic measurement of voltage noise.
10.8.2 Contactless earthing resistance measurement using two
current clamps
(10% of reading + 10 digits)
*)
Distance between test clamps > 30 cm.
Additional error at 3 V voltage noise (50 Hz) ...........10 % of reading
Test voltage frequency ...........................................125 Hz
Noise current indication ..........................................yes
Low clamp current indication ..................................yes
Additional clamp error has to be considered.