1.6.5 WIRING HOLD INPUT
Displayed value is held with an external HOLD command input.
Connect the contact across HOLD to COM as shown in the following gure.
Close the contact to hold the value.
Detecting voltage Approx. 5 V DC, 1 mA
Detecting level ≤ 1.5 V
IMPORTANT
• Be sure to conrm the input polarity in wiring.
• Isolate with a photo-coupler or a relay as the HOLD input is not isolated to the AC input signal.
HOLD input
COM HOLD
34
■ WIRING EXAMPLES
L
HOLD
H
L
HOLD
H
Twisted pair cable
Twisted pair cable
3
4
COM
(a)
Photo-Coupler
(b)
Relay
Relay
Photo-Coupler
HOLD
3
4
COM
HOLD