EasyManua.ls Logo

MG 40 Series - Wiring Hold Input

MG 40 Series
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1440DCT EM-9538-B Rev.5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
1.6.5 WIRING HOLD INPUT
Displayed value is held with an external HOLD command input.
Connect the contact across HOLD to COM as shown in the following gure.
Close the contact to hold the value.
Detecting voltage Approx. 5 V DC, 1 mA
Detecting level 1.5 V
IMPORTANT
• Be sure to conrm the input polarity in wiring.
• Isolate with a photo-coupler or a relay as the HOLD input is not isolated to the AC input signal.
HOLD input
HOLD command signal
COM HOLD
34
WIRING EXAMPLES
L
HOLD
H
L
HOLD
H
Twisted pair cable
Twisted pair cable
3
4
COM
(a)
Photo-Coupler
(b)
Relay
Relay
Photo-Coupler
HOLD
3
4
COM
HOLD

Table of Contents