2. BASIC SETTING AND OPERATION
2.1 BASIC SETTING
This section describes ow and procedure of the basic setting.
The following shows the ow and procedure to set the CT secondary to 0 – 1 A AC and the CT primary to 0.0 – 300.0 A AC
with the input code ‘A4’ as an example.
2.1.1 BASIC SETTING FLOW
The basic setting is as shown in the following owchart.
2.1.2 RELATION BETWEEN INPUT SCALING AND DISPLAY SCALING
The relation between input scaling and display scaling is as shown in the following gure and chart.
Input scaling: 0% input value (input scaling value A) and 100% input value (input scaling value B)
Display scaling: 0% display value (display scaling value A) and 100% display value (display scaling value B)
Power ON
Starting measurement
Setting input scaling value A
Setting display scaling value A
Setting input scaling value B
Setting display scaling value B
Setting decimal point position
0.000 A
Input scaling value A
0.000 A
Display scaling value A
0.0 A
Input signal
Input scaling
Display scaling
1.000 A
Input scaling value B
1.000 A
Display scaling value B
300.0 A
Display value
300.0 A
0.0 A
0.000 A 1.000 A
Input value
Code ‘A4’ : 0.000 – 1.000 A AC