2.1.4 BASIC SETTING PROCEDURE
The following shows the procedure to set the CT secondary to 0 – 1 A AC and the CT primary to 0.0 – 300.0 A AC as an
example. Set values meeting signals to use. Refer to 3. SETTING SCALING VALUES for details of setting.
PARAMETER LIST FOR BASIC SETTING
Parameters used in the basic setting are as shown in the following table.
PARAMETER SETTING VALUE SETTING
Decimal point position 888.8 1 decimal place (10
-1
)
Input scaling value A 0.000 0% input: 0.000 A
Input scaling value B 1.000 100% input: 1.000 A
Display scaling value A 000.0 0% display: 0.0 A
Display scaling value B 300.0 100% display: 300.0 A
BASIC SETTING PROCEDURE
The basic setting procedure is as follows.
1
Conrm the wiring, turn on the power and move on to Scaling Setting Mode (measurement stopped).
• Hold down S
CALE/ button for 3 seconds or more.
2
Set decimal point position.
• Press S
HIFT button to shift the display into the setting standby mode and UP button to select the decimal point posi-
tion.
• Press S
HIFT button to apply the new setting.
3
Set input scaling value A.
• Press D
ISP/ or SCALE/ button to go to the next or previous parameter setting.
• Press S
HIFT button to show the current setting and SCALE/ button to shift the display into the setting standby mode.
• Press D
ISP/ or SCALE/ button to go to the next digit and UP button to change the blinking value.
• Press S
HIFT button to apply the new setting.
4
Set input scaling value B.
• Press D
ISP/ or SCALE/ button to go to the next or previous parameter setting.
• Press S
HIFT button to show the current setting and SCALE/ button to shift the display into the setting standby mode.
• Press D
ISP/ or SCALE/ button to go to the next digit and UP button to change the blinking value.
• Press S
HIFT button to apply the new setting.
5
Set display scaling value A.
• Press D
ISP/ or SCALE/ button to go to the next or previous parameter setting.
• Press S
HIFT button to show the current setting and SCALE/ button to shift the display into the setting standby mode.
• Press D
ISP/ or SCALE/ button to go to the next digit and UP button to change the blinking value.
• Press S
HIFT button to apply the new setting.
6
Set display scaling value B.
• Press D
ISP/ or SCALE/ button to go to the next or previous parameter setting.
• Press S
HIFT button to show the current setting and SCALE/ button to shift the display into the setting standby mode.
• Press D
ISP/ or SCALE/ button to go to the next digit and UP button to change the blinking value.
• Press S
HIFT button to apply the new setting.
7
Return to Measuring Mode (measurement started).
• Hold down D
ISP/ or SCALE/ button for 1 second or more to return to Measuring Mode.