2940DCT EM-9538-B Rev.5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
3.3 STEP 3. INPUT SCALING VALUE B
3.3.1 OPERATING PROCEDURE
1
Conrm the wiring, and turn on the power.
• All the indications turn on for approximately 3 seconds and then the
display moves on to Measuring Mode.
NOTE
Indication ‘S.ERR’ may blink, which shows the input out of the permis-
sible range and does not show the unit failure.
2
Hold down SCALE/↑ button for 3 seconds or more to move on to
Scaling Setting Mode.
• The setting item ‘D PT’ (decimal point position) is indicated.
3
Press DISP/↓ or SCALE/↑ button to go to the input scaling value B
setting.
• The setting item ‘I SP’ (input scaling value B) is indicated.
NOTE
Skip to Step 7 if the default value is acceptable.
3,5
2,3,
4,5
4,6
5
■
Immediately after power on (all indicators on)
■ Measuring Mode
*1 Display depends on the settings and input.