3540DCT EM-9538-B Rev.5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
4. OPERATION
Make sure that 0.0 – 300.0 A AC is correctly indicated according to the input 0 – 1 A AC provided.
IMPORTANT
Before operating, make sure that the wiring is correct, the input and the power supply are within the specication range.
1
Apply 0 A input (0%) and make sure that 0.0 A is indicated.
NOTE
■ WHEN THE FOLLOWING IS INDICATED…
• When ‘S.ERR’ is indicated, the input is not applied correctly. Check the input wir-
ing, equipment and signal.
• When ‘ERR’ is indicated, the input scaling value A or B is not set correctly. Return
the setting within the valid range.
Blinking
Blinking
2
Apply 0.5 A input (50%) and make sure that 150.0 A is indicated.
3
Apply 1 A input (100%) and make sure that 300.0 A is indicated.
*1 Display depends on the settings and input.