5440DCT EM-9538-B Rev.5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
13.2 MODEL NUMBERING
Code number: 40DCT–[1]–[2][3]
[1] INPUT
Current
A1: 0.00 – 20.00 mA AC (input resistance 5 Ω)
A2: 0.0 – 200.0 mA AC (input resistance 0.5 Ω)
A3: 0.000 – 2.000 A AC (input resistance 0.05 Ω)
A4: 0.000 – 1.000 A AC (input transformer burden 0.1 VA)
A5: 0.000 – 5.000 A AC (input transformer burden 0.5 VA)
[2] POWER INPUT
AC Power
K3: 100 – 120 V AC (operational voltage range 85 – 132 V, 47 – 66 Hz)
L3: 200 – 240 V AC (operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R: 24 V DC (operational voltage range 24 V ±20%, ripple 10% p-p max.)
[3] OPTIONS
Blank: None
/Q: With options (specify the specication)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
Moving parts and indicators are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet (No. ESU-9538)