3. DISPLAY SCALING SETTING
The display scaling setting with the input codes ‘Sx’ (with scaling function) (hereafter called process meter) is as shown in
the following owchart.
NOTE
With the input codes ‘Vx’ (without scaling function) (hereafter called DC voltmeter), the display scaling setting is not appli-
cable. Refer to 5. OPERATION to conrm the indication, and 10.1 DC VOLTMETER CALIBRATION to correct deviation if
necessary.
3.1 DISPLAY SCALING SETTING PROCEDURE WITH PROCESS METER
The following shows the procedure to set the input to 0 – 10 mA DC and the display to 0.0 – 100.0% with the input code
‘SC’ as an example. Set values meeting signals of equipment to use. Refer to 4. SETTING DISPLAY SCALING for details
of setting.
PARAMETER LIST FOR BASIC SETTING
Parameters used in the basic setting are as shown in the following table.
PARAMETER SETTING VALUE SETTING
Display scaling value A
0000
*1
0% display: 0.0%
Display scaling value B
1000
*1
100% display: 100.0%
Decimal point position 888.8 1 decimal place (10
-1
)
*1 The decimal point position depends on the decimal point position setting.
Power ON
Starting measurement
Setting display scaling value A
Setting display scaling value B
Setting decimal point position