10.1.2 OPERATING PROCEDURE
1
Hold down SC button for 3 seconds or more to move on to Cali-
bration Mode.
• 0% input calibration is indicated.
NOTE
Warm up the unit for 10 minutes or more before carrying out the calibration.
2
Apply 0% input and press UP button to register the value.
• 0% input calibration is registered.
IMPORTANT
Conrm that the input signal is stable before pressing UP button.
3
Press DI button to go to the 50% input calibration.
• 50% input calibration is indicated.
4
Apply 50% input and press UP button to register the value.
• 50% input calibration is registered.
IMPORTANT
Conrm that the input signal is stable before pressing UP button.
3,5,
7
1,7
2,4,
6