13. APPENDICES
13.1 SPECIFICATIONS
■ GENERAL SPECIFICATIONS
Construction Panel ush mounting
Connection Terminal block “S” Screwless spring terminal
Applicable wire size 1.0 to 1.3 mm
2
, stripped length 8 mm
Terminal block “D” Separable screwless spring terminal
Applicable wire size 1.0 to 1.3 mm
2
, stripped length 8 mm
Housing material Flame-resistant resin (gray)
Isolation Input to power
Setting (front button)
Scaling setting mode
*1
Display scaling value A, display scaling value B, decimal point position
Calibration mode
*2
0% calibration, 50% calibration, 100% calibration
Display setting mode Moving average, brightness, initialization, version indication
A/D conversion ∑ – Δ
Sampling rate 5 times/sec. (200 msec.)
Averaging None or moving average
*1 With process meter
*2 With DC voltmeter
■ DISPLAY
Display 4 digits of 10.2 mm (0.4 inch) height, 7-segment, red LED
Display range -1999 to 9999
Zero indication Higher-digit zeros are suppressed
DC voltmeter Over-range indication ‘S.ERR’ blinks when out of the input range.
Process meter Scaling range for meas-
urement range
(conformance range)
-1999 to 9999 counts
Decimal point position 10
-1
, 10
-2
, 10
-3
or none
Over-range indication ‘-1999’ or ‘9999’ blinking for display values out of the display range.
‘S.ERR’ blinks surpassing the permissible range.
■ INPUT SPECIFICATIONS
DC voltmeter Input code: V1 Measurement range (conformance range) ±199.9 mV DC
Input range -219 – +219 mV
Input resistance ≥ 1 MΩ
Input code: V2 Measurement range (conformance range) ±1.999 V DC
Input range -2.19 – +2.19 V
Input resistance ≥ 1 MΩ
Input code: V3 Measurement range (conformance range) ±19.99 V DC
Input range -21.9 – +21.9 V
Input resistance ≥ 1 MΩ