Midea Aqua thermal Super Service Manual
6 Drive Module Failure
6.1 Check code table
Error code
Content
Error category
Need to power on again
L10
Overcurrent protection
Overcurrent fault
NO
L11
Transient phase current overcurrent protection
NO
L12
Phase current overcurrent lasts 30s protection
NO
L20
Module over temperature protection
Over temperature fault
NO
L30
Low bus voltage error
Power fault
NO
L31
High bus voltage error
NO
L32
Excessively high bus voltage error
NO
L34
Phase loss error
NO
L43
Current sampling bias is abnormal
hardware fault
NO
L45
Motor code not match
YES
L46
IPM protection (FO)
NO
L47
Module type not matchAfter module resistance detection
YES
L50
Startup failure
Control fault
NO
L51
Out of step errorReserved
NO
L52
Zero speed protection
NO
L60
Fan motor phase loss protection
Diagnostic fault
NO
L65
IPM short circuit error
NO
L66
FCT detection error
NO
L6A
Open circuit of U-phase upper tube
NO
L6b
Open circuit of U-phase lower tube
NO
L6C
Open circuit of V-phase upper tube
NO
L6d
Open circuit of V-phase lower tube
NO
L6E
Open circuit of W-phase upper tube
NO
L6F
Open circuit of W-phase lower tube
NO
Lb0
High pressure switch motion
Authentication fault
NO
Lb1
Relay adhesionReserved
NO
Lb2
RAM check errorReserved
NO
Lb3
ROM check errorReserved
NO
Lb4
Register or ALU check errorReserved
NO
Lb5
Stack over flow check errorReserved
NO
Lb6
Program stream check errorReserved
NO
Lb7
Other abnormal check /PED diagnostic errors
NO
Lb8
PED 5V abnormalReserved
NO
MBT Confidential