In the ventilation mode .When ventilating, the compressor, outdoor blower fan, four-way valve and electric 
heating are all closed and the indoor blower fan is running at the set speed. 
Automatic mode 
●  Conditions for entering the automatic running mode are: After power-up for the first time, start up and select 
the automatic operating mode of remote or press emergency key, the working mode depends on Tr and if the 
working mode had set , it doesn’t change by Tr and the default set temperature is 25  ℃. 
Time on and time off 
When the time on or time off is used, the clock of remote controller shall be corresponding to the current clock 
and the timing times is less than or equal to 24 hours, when the timing time is reached, unit will start-up or 
shutdown. 
Sleep function 
 
      When the sleep key is press, air conditioner enter sleep state, indoor blower fan running at low speed, only sleep 
indication display. 
 
Emergency key function 
 
There is a forcible execution key on the panel of indoor units and the air conditioner can run by pressing the key 
when the remote control is out of work or missing. 
When pressing down the forcible execution key, then power up and enter the self-check program. 
 
     Failure display 
LED lamp display 
code explain  code  explain
failure The reason of fault and solution 
DF 
display at 
on state 
flicker 1/1 
SEC 
 
defrost 
indication 
Normal, the    defrost state is removed, it will 
return to normal condition automatically 
 
display at 
off state 
flicker 1/3 
SEC 
  anti cold wind 
1、 Normal (during heating mode ) 
2、It will be removed when the coil pipe 
temperature sensor reaches certain 
temperature. 
E2 
display at 
off state 
flicker 1/1 
SEC 
display 
at on/off 
state 
 room temp. 
sensor fault 
1、Check whether the resistance of the 
sensor is normal (the resistance is 5КΩ in 
the normal temperature 25℃), when it is 
abnormal the sensor should be replaced.
2、Check whether there is short circuit or 
open circuit in the wire of the sensor, and 
whether the plug is connected well, 
whether there is welding off or rosin joint 
on the electric control board, if there is 
any, it should be repaired. 
3、When the 1 and 2 are both normal, then 
the components or integrated circuit is 
damaged, the electric control board 
should be replaced. 
E3 
display at 
off state 
flicker 3/5 
SEC 
display 
at on/off 
     coil temp. 
sensor fault 
1 、 Check whether the resistance of the 
sensor is normal (the resistance is 5КΩ in