IPM module protecon
Check whether the voltage range
of P-N on IPM module is normal
DC277-356V for 18-27KBtu/h;
DC277-410V for 36-48KBtu/h
Yes
Yes
No
Yes
Check whether the input
power supply is correct
208-230V, 1N, 60Hz
No No
Regulate it to correct, then
check whether the system
can work normally
Check whether the
power supply line is
connected correctly and
ght
Yes
Connect it correctly
and ght
No
Is the connecng line between
main board and the
IPM module is well
connected?
Yes
No
No
No
Is the connecng compressor
line connected
correctly and ght?
Replace the IPM module,
check whether the system can
work normally?
No
No
Replace the main board; check
whether the system can work
normally
No
Replace the compressor, check
whether the system can work
normally
Check whether the lines
in E-part box are
connected ght
Yes
No
No
Yes
No
Replace the bridge recfiers
Check whether the bridge recfiers are
normal. Use the mulmeter to measure
the resistance between the two
terminals. Check whether the resistance
value is 0.
Replace the connecng line or
reactor or replace the PFC
module(for M4OF-36HFN1-
M&M5OF-48HFN1-M)
Yes
No
No
Yes
Problem solved
Check if the outdoor fan
runs properly or the outdoor
unit venlaon is good.
No
Refer to the Fan Speed is Out
of Control. Determine the
cause and resolve.
Yes
Yes
Yes
Connect it correctly
and ght
Connect it correctly
and ght
Connect it correctly
and ght
Is the connecting line for every reactor
normal? If the line is broken,
the resistance of the two ports is
Check if the PFC broken module
(for M4OF-36HFN1-M & M5)F-48HFN1-m)
DLCM(R/H)B: Service Manual