DIAGNOSIS AND SOLUTION (CONT)
Indoor and outdoor unit communication error (EL01)
Remarks:
Use a multimeter to test the DC voltage between the outdoor unit’s 2 port and 3 port. The red pin of multimeter connects with the 2 port
while the black pin is for 3 port.
When the air conditioner is normal running, the voltage is moving alternately as positive values and negative values.
If the outdoor unit has a malfunction, the voltage has always been the positive value.
If the indoor unit has malfunction, the voltage is a fixed value.
Fig. 20 — Multimeter
Use a multimeter to test the resistance of the reactor that does not connect with the capacitor.
The normal value should be around zero ohm, otherwise the reactor has malfunctioned.
Fig. 21 — Multimeter