DIAGNOSIS AND SOLUTION (CONT)
Over voltage or too low voltage protection (PC01)
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
Power supply issues
System leakage or blockage
Faulty PCB
Reactor
Troubleshooting and Repair:
Check the power supply.
Is it in working order ?
NO
Check the connections and wires.
YES
Are they in working order ?
Ensure proper connections or
replace the wires.
NO
Power on and measure the
voltage between P and N.
YES
Replace the IPM board.NO
Check the reactor.
YES
Is it in working order ?
Replace outdoor PCB.NO
Replace the reactor.
YES
While the unit is in STANDBY
mode, is the voltage between P and N
around DC 310V, 340V, or 380V?
When starting the unit, is the unit
in the 220V~400V range?